Specifications
|
|
| |
|
|
Input
|
|
Input Voltage
|
|
90-264 VAC
|
|
Input Frequency
|
|
47-63 Hz
|
|
Input Current
|
|
0.6 A rms max
|
|
Inrush Current
|
|
50 A max at 264 VAC
|
|
Input Protection
|
|
Fitted with a T2 A/250 VAC fuse in live line
|
| |
|
|
|
Output
|
|
Output Voltage
|
|
See table
|
|
Initial Set Accuracy
|
|
±2% set at 60% load
|
|
Minimum Load
|
|
No minimum load required
|
|
Start Up Delay
|
|
3 s max
|
|
Start Up Rise Time
|
|
2 ms
|
|
Hold Up Time
|
|
16 ms minimum at 115 VAC
|
|
Line Regulation
|
|
±1%
|
|
Load Regulation
|
|
See datasheet
|
|
Transient Response
|
|
5% max deviation, recovering to within 1% within 500 µs for a 50% load change
|
|
Ripple & Noise
|
|
1% max, 20 MHz BW
|
|
Overvoltage Protection
|
|
See datasheet
|
|
Overload Protection
|
|
120-150%
|
|
Short Circuit Protection
|
|
Trip & restart (hiccup mode), auto recovery
|
|
Temperature Coefficient
|
|
±0.05%/°C
|
| |
|
|
|
General
|
|
Efficiency
|
|
82% typical
|
|
Isolation
|
|
4000 VAC Input to Output
|
|
Switching Frequency
|
|
70 kHz typical
|
|
Power Density
|
|
3 W/inch3
|
|
MTBF
|
|
500 kHrs to MIL-STD-217F
|
| |
|
|
|
Environmental
|
|
Operating Temperature
|
|
0 °C to +60 °C, derate from 100% load at +40 °C to 60% load at +60 °C for 5, 9 & 12 V models. Derate from 100% load at +50 °C to 80% load at +60 °C for 15, 18 & 24 V models
|
|
Cooling
|
|
Natural convection
|
|
Operating Humidity
|
|
15-95% non-condensing
|
|
Storage Temperature
|
|
-20 °C to +85 °C
|
|
Operating Altitude
|
|
3000 m
|
|
Vibration
|
|
5-500 Hz at 3 g for 10 mins on each axis
|
|
Shock
|
|
30 g with 18 ms half sine wave, 3 times on each axis
|
| |
|
|
|
EMC and Safety
|
|
Emissions
|
|
EN55011 Level B conducted & radiated
|
|
Harmonic Currents
|
|
EN61000-3-2
|
|
Voltage Flicker
|
|
EN61000-3-3
|
|
ESD Immunity
|
|
EN610000-4-3 Level 3, Perf Criteria A
|
|
Radiated Immunity
|
|
EN61000-4-3 Level 2, Perf Criteria A
|
|
EFT/Burst
|
|
EN61000-4-4 Level 3, Perf Criteria A
|
|
Surge
|
|
EN61000-4-5 Level 3, Perf Criteria A
|
|
Conducted Immunity
|
|
EN61000-4-6 Level 3, Perf Criteria A
|
|
Dips & Interruptions
|
|
EN61000-4-11, 70% 500 ms, 40% 100 ms, <5% 5000 ms, Perf Criteria A, B, B
|
|
Safety Approvals
|
|
UL60601-1, EN60601-1, IEC60601-1, CE Mark
|