Specifications
|
|
| |
|
|
Input
|
|
|
Input Voltage
|
|
90-264 VAC
|
|
|
|
Input Frequency
|
|
47-63 Hz
|
|
|
|
Input Current
|
|
60 A at 115 VAC, 120 A at 230 VAC, cold start +25 °C
|
|
|
|
Power Factor
|
|
0.95 typical
|
|
|
|
Earth Leakage Current
|
|
150 μA max at 115 VAC, 250 μA max at 230 VAC
|
|
|
|
No Load Input Power
|
|
<0.5 W
|
|
|
| |
|
|
|
|
|
Output
|
|
|
Output Voltage
|
|
See datasheet
|
|
|
|
Output Voltage Trim
|
|
Not user-adjustable
|
|
|
|
Initial Set Accuracy
|
|
±2%
|
|
|
|
Minimum Load
|
|
No minimum load required
|
|
|
|
Start Up Delay
|
|
5 s max at 100 VAC
|
|
|
|
Hold Up Time
|
|
3 ms minimum at 100 VAC
|
|
|
|
Line Regulation
|
|
±0.5% maximum
|
|
|
|
Load Regulation
|
|
See datasheet
|
|
|
|
Transient Response
|
|
4% max. deviation, recovery to within 1% in 500 μs for a 25% load change
|
|
|
|
Ripple & Noise
|
|
2% max pk-pk (see note 1 of datasheet)
|
|
|
|
Overvoltage Protection
|
|
110-140% Vnom, recycle input to reset
|
|
|
|
Short Circuit Protection
|
|
Trip and restart (Hiccup mode)
|
|
|
|
Overvoltage Protection
|
|
Unit shuts down, recycle input to reset
|
|
|
|
Temperature Coefficient
|
|
0.04%/°C
|
|
|
| |
|
|
|
|
|
General
|
|
|
Efficiency
|
|
88% min
|
|
|
|
Isolation
|
|
3000 VAC Input to Output 1500 VAC Input to Ground Output 0 V is electrically connected to Input Ground
|
|
|
|
Switching Frequency
|
|
20-80 kHz variable
|
|
|
|
Power Density
|
|
5.1 W/In3
|
|
|
|
MTBF
|
|
>100 kHrs per MIL-HDBK-217F (+25 °C ambient at full load)
|
|
|
| |
|
|
|
|
|
Environmental
|
|
|
Operating Temperature
|
|
0 °C to +70 °C, derate from 100% power at +40 °C to 60% power at +70 °C
|
|
|
|
Operating Humidity
|
|
10-95% RH, non-condensing
|
|
|
|
Storage Temperature
|
|
-20 °C to +80 °C
|
|
|
|
Operating Altitude
|
|
3000 m
|
|
|
|
Shock
|
|
30 g, 10 ms on 3 axes
|
|
|
|
Vibration
|
|
5-100 Hz, 2.31 m/s2, 20 mins, 3 axes
|
|
|
| |
|
|
|
|
|
EMC and Safety
|
|
|
Emissions
|
|
EN55022/FCC/VCCI, Class B conducted EN55022/FCC/VCCI, Class B radiated
|
|
|
|
Harmonic Currents
|
|
EN61000-3-2
|
|
|
|
Voltage Flicker
|
|
EN61000-3-3
|
|
|
|
ESD Immunity
|
|
EN61000-4-2, ±15 kv contact and air discharge
|
|
|
|
Radiated Immunity
|
|
EN61000-4-3, level 2 Perf Criteria A
|
|
|
|
EFT/Burst
|
|
EN61000-4-4, level 2 Perf Criteria A
|
|
|
|
Surge
|
|
EN61000-4-5, level 3 Perf Criteria A
|
|
|
|
Conducted Immunity
|
|
EN61000-4-6, level 2 Perf Criteria A
|
|
|
|
Dips & Interruptions
|
|
EN61000-4-11, 30% for 10 ms, 60% 100 ms, 100% 5000 ms, Perf Criteria A, B, B
|
|
|
|
Safety Approvals
|
|
EN60950, UL60950, CSA22.2 No. 60950 per cUL, CE Mark
|
|
|