AC-DC电源,DC-DC转换器,开关电源模块 - XPPower
医疗电源>>15 - 175W
AEM 系列
• 60W
• 符合能源之星标准
• 符合医疗等级安规认证
• 4000 VAC 绝缘
• 符合Class II 应用标准
• 单输出5 V - 48 V
 
Short Form Datasheet.pdf
73.64 K
 
 
Specifications
 
     
Input
Input Voltage
 
90-264 VAC
 
 
Input Frequency
 
47-63 Hz
 
 
Input Current
 
0.6 A rms max
 
 
Inrush Current
 
80 A max at 264 VAC
 
 
Input Protection
 
Fitted with a T2 A/250 VAC fuse in live line
 
 
No Load Input Power
 
<0.5 W for ≥12 V output
 
 
         
Output
Output Voltage Trim
 
See datasheet
 
 
Initial Set Accuracy
 
±2% set at 60% load
 
 
Minimum Load
 
No mimimum load required
 
 
Start Up Delay
 
3 s max
 
 
Start Up Rise Time
 
2 ms
 
 
Hold Up Time
 
8 ms minimum at 115 VAC
 
 
Line Regulation
 
±1%
 
 
Transient Response
 
5% max deviation recovering to within 1% within 500 µs for 50% load change
 
 
Ripple & Noise
 
1% max, 20 MHz BW see note 2
 
 
Overvoltage Protection
 
See datasheet
 
 
Overload Protection
 
120-150%
 
 
Short Circuit Protection
 
Trip & restart (hiccup mode), auto-recovery
 
 
Temperature Coefficient
 
±0.05%/°C
 
 
         
General
Efficiency
 
85%, See datasheet
 
 
Isolation
 
4000 VAC Input to Output
 
 
Switching Frequency
 
70 kHz typical
 
 
Power Density
 
4.2 W/Inch
 
 
MTBF
 
500 kHrs to MIL-STD-217F
 
 
         
Environmental
Operating Temperature
 
0 °C to +60 °C, derate from 100% load at +40 °C to 50% load at +60 °C
 
 
Cooling
 
Convection-cooled
 
 
Operating Humidity
 
15-95% non-condensing
 
 
Storage Temperature
 
-20 °C to +85 °C
 
 
Operating Altitude
 
3000 m
 
 
Vibration
 
5-500 Hz at 3 g for 10 mins on each axis
 
 
Shock
 
30 g with 18 ms half sine wave, 3 times on each axis
 
 
         
EMC and Safety
Emissions
 
EN55011 Level B conducted & radiated
 
 
Harmonic Currents
 
EN61000-3-2
 
 
Voltage Flicker
 
EN61000-3-3
 
 
ESD Immunity
 
EN61000-4-2 Level 3, Perf Criteria A
 
 
Radiated Immunity
 
EN61000-4-3 Level 2, Perf Criteria A
 
 
EFT/Burst
 
EN61000-4-4, Level 3, Perf Criteria A
 
 
Surge
 
EN61000-4-5 Level 3, Perf Criteria A
 
 
Conducted Immunity
 
EN61000-4-6 Level 3, Perf Criteria A
 
 
Dips & Interruptions
 
EN61000-4-11, 70% UT for 500 ms, 40% UT for 100 ms, <5% UT for 5000 ms, Perf criteria A, B, B
 
 
Safety Approvals
 
UL60601-1, EN60601-1, IEC60601-1, CE Mark
 
 
 
 
 
 
 
 
 
     Model Number
      Input
   Output
  Power
 
 
 
 
 
 
 
 
AEM60US05
90-264 VAC
8 V/6 A
60 W
 
 
AEM60US12
90-264 VAC
12 V/5 A
60 W
 
 
AEM60US15
90-264 VAC
15 V/4 A
60 W
 
 
AEM60US18
90-264 VAC
18 V/3.33 A
60 W
 
 
AEM60US19
90-264 VAC
19 V/3.15 A
60 W
 
 
AEM60US24
90-264 VAC
24 V/2.5 A
60 W
 
 
AEM60US36
90-264 VAC
36 V/1.66 A
60 W
 
 
AEM60US48
90-264 VAC
48 V/1.25 A
60 W
 
 
 
 
 
 
 
 
请填写您的E-mail地址,确定接受我们定期更新的产品信息!

Email地址