Specifications
|
|
| |
|
|
Input
|
|
|
Input Voltage
|
|
80-264 VAC, derate output power 10% <90 VAC and 20% <85 VAC
|
|
|
|
Input Frequency
|
|
47-63 Hz
|
|
|
|
Input Current
|
|
40 A max at 264 VAC
|
|
|
|
Power Factor
|
|
EN61000-3-2 class A compliant
|
|
|
|
Earth Leakage Current
|
|
250 µA max 264 VAC 60 Hz
|
|
|
|
Input Protection
|
|
T 16 A / 250 V internal fuse in line and neutral
|
|
|
| |
|
|
|
|
|
Output
|
|
|
Output Voltage
|
|
12-48 VDC (see tables)
|
|
|
|
Output Voltage Trim
|
|
±10% V1
|
|
|
|
Initial Set Accuracy
|
|
±1% V1, ±5% V3
|
|
|
|
Minimum Load
|
|
No minimum load required
|
|
|
|
Start Up Delay
|
|
500 ms max
|
|
|
|
Start Up Rise Time
|
|
50 ms typical
|
|
|
|
Hold Up Time
|
|
20 ms minimum
|
|
|
|
Drift
|
|
±0.2% after 20 min warm up
|
|
|
|
Line Regulation
|
|
±0.5% maximum
|
|
|
|
Load Regulation
|
|
±1% V1, ±5% V3
|
|
|
|
Transient Response
|
|
4% max. deviation, recovery to within 1% in 500 µs for a 50-75-50% load change
|
|
|
|
Ripple & Noise
|
|
1% pk-pk V1, 20 MHz bandwidth
|
|
|
|
Overvoltage Protection
|
|
115-145% Vnom, recycle input to reset
|
|
|
|
Overtemperature Protection
|
|
Auto reset
|
|
|
|
Overload Protection
|
|
110-140%, V1 only
|
|
|
|
Short Circuit Protection
|
|
Auto recovery
|
|
|
|
Temperature Coefficient
|
|
0.05% / ºC
|
|
|
|
Remote Sense
|
|
Compensates for 0.5 V total voltage drop
|
|
|
|
Remote On/Off
|
|
Uncommitted isolated optocoupler diode, powered diode inhibits V1 & V2 fan supply
|
|
|
|
Current Share
|
|
Single wire current share
|
|
|
| |
|
|
|
|
|
General
|
|
|
Efficiency
|
|
86% typical
|
|
|
|
Isolation
|
|
4000 VAC input to output, 1500 VAC input to ground, 500 VDC output to ground
|
|
|
|
Switching Frequency
|
|
PFC 70 KHz, main converter 200 KHz
|
|
|
|
Power Density
|
|
8.2 W/in3
|
|
|
|
Signals
|
|
AC OK, remote on/off, current share
|
|
|
|
MTBF
|
|
300 KHrs to MIL-HDBK-217 at 25 ºC, GB
|
|
|
| |
|
|
|
|
|
|
|
|
Operating Temperature
|
|
-20 °C to +70 °C, derate linearly from +50 ºC at 2.5% / ºC to 50% load at +70 ºC
|
|
|
|
Cooling
|
|
Forced cooled, ‘-TF’ & ‘-EF’ models have integral dual voltage level fan, which is load dependant, U Channel requires 5.5 m/s minimum airflow
|
|
|
|
Operating Humidity
|
|
95% RH, non-condensing
|
|
|
|
Storage Temperature
|
|
-40 °C to +85 °C
|
|
|
|
Operating Altitude
|
|
3000 m
|
|
|
|
Shock
|
|
30 g pk, half sine, 6 axes
|
|
|
|
Vibration
|
|
2 g rms, 5 Hz to 500 kHz, 3 axes
|
|
|
| |
|
|
|
|
|
EMC and Safety
|
|
|
Emissions
|
|
EN55022 level B conducted, EN55022 level A radiated
|
|
|
|
Harmonic Currents
|
|
EN61000-3-2, class A
|
|
|
|
Voltage Flicker
|
|
EN61000-3-3
|
|
|
|
Radiated Immunity
|
|
EN61000-4-3, level 3 Perf Criteria A
|
|
|
|
EFT/Burst
|
|
EN61000-4-4, level 3 Perf Criteria A
|
|
|
|
Surge
|
|
EN61000-4-5, installation class 3, Perf Criteria A
|
|
|
|
Conducted Immunity
|
|
EN61000-4-6, level 3, Perf Criteria A
|
|
|
|
Dips & Interruptions
|
|
EN61000-4-11, 30% 10 ms, 60% 100 ms, 100% 5000 ms, Perf Criteria A, B, B, EN60601-1-2, 30% 500 ms, 60% 100 ms, 100% 10 ms, 100% 5000 ms, Perf Criteria A, A, A, B - 230 VAC. Consult longform datasheet for 115 V operation.
|
|
|
|
Safety Approvals
|
|
IEC60601-1 CB report, CSA 22.2 No. 60601-1, UL60601-1, TUV, EN60601-1
|
|
|