Specifications
|
|
|
|
|
|
|
Input Voltage
|
|
85-264 VAC (120-370 VDC). Full power at 90 VAC derate by 10% at 85 VAC
|
|
|
|
Input Frequency
|
|
47-63 Hz, 400 Hz (unit meets all specs at 400 Hz, except leakage current)
|
|
|
|
Input Current
|
|
X4: 5.33 A at 115 VAC, 2.67 A at 230 VAC. X5: 6.67 A at 115 VAC, 3.33 A at 230 VAC. X7: 9.33 A at 115 VAC, 4.67 A at 230 VAC. X9: 12.0 A at 115 VAC, 6.0 A at 230 VAC. X10: 13.3 A at 115 VAC, 6.67 A at 230 VAC.
|
|
|
|
Inrush Current
|
|
X4, X5 & X7 <20 A, X9 & X10 <40 A
|
|
|
|
Power Factor
|
|
0.99 typical at 115 VAC & 230 VAC full load
|
|
|
|
Earth Leakage Current
|
|
X models <1.5 mA at 264 VAC/50Hz, XM models <200 µA at 264 VAC/50 Hz
|
|
|
|
Input Protection
|
|
Dual fusing, line & neutral
|
|
|
|
|
|
|
Output Power
|
|
See datasheet. Chassis can deliver an extra 200 W at high line (180-264 VAC)
|
|
|
|
Output Voltage
|
|
See datasheet
|
|
|
|
Output Voltage Trim
|
|
±10%
|
|
|
|
Minimum Load
|
|
No minimum load required for 2 slot or 3 slot single output modules. 2 slot dual outputs required 10% load on V1 to meet specified regulation on V2 output
|
|
|
|
Start Up Delay
|
|
2 s max
|
|
|
|
Hold Up Time
|
|
20 ms from 90 VAC input and full output load
|
|
|
|
Line Regulation
|
|
<0.1%
|
|
|
|
Load Regulation
|
|
<1.0%
|
|
|
|
Ripple and Noise
|
|
50 mV or 1% pk-pk at 20 MHz BW, whichever is greater
|
|
|
|
Overvoltage Protection
|
|
115-130% Vnom
|
|
|
|
Overload Protection
|
|
110-140%
|
|
|
|
Overtemperature Protection
|
|
115 °C measured internally, recycle mains to reset
|
|
|
|
Short Circuit protection
|
|
Continuous
|
|
|
|
Temperature Coefficient
|
|
0.03%/°C
|
|
|
|
Remote Sense
|
|
Compensates for up to 0.5 V drop
|
|
|
|
Enable/Inhibit
|
|
See datasheet
|
|
|
|
Current Share
|
|
See datasheet
|
|
|
|
Housekeeping Voltage
|
|
5 V/1 A from each chassis
|
|
|
|
|
|
|
Efficiency
|
|
83.5 % typical at 115 VAC
|
|
|
|
Isolation
|
|
4000 VAC Input to Output, 1500 VAC Input to Ground, 250 VDC Output to Ground
|
|
|
|
Switching Frequency
|
|
60 kHz typ PFC, 200 kHz typ modules
|
|
|
|
Signals
|
|
See datasheet
|
|
|
|
MTBF
|
|
225 kHrs to MIL-217F at +25 °C
|
|
|
|
|
|
|
Operating Temperature
|
|
-20 °C to +70 °C. For operation above +50 °C derate linearly to 50% load at +70 °C. Reverse air option derate from +40 °C to half load at +60 °C
|
|
|
|
Storage Temperature
|
|
-40 °C to +85 °C
|
|
|
|
Cooling
|
|
Forced-air cooling (via field-replaceable internal fan)
|
|
|
|
Operating Humidity
|
|
5-95% RH, non-condensing
|
|
|
|
Operating Altitude
|
|
3000 m at full specification
|
|
|
|
Shock
|
|
MIL-STD-810 Method 516.4 Procedure 1, 30 g half sine, 6 axis
|
|
|
|
Vibration
|
|
MIL-STD-810 Method 514.4 Procedure 1, 1 g 5-500 Hz, 3 axis
|
|
|
|
|
|
|
Emissions
|
|
X version: EN55022 (CISPR22) Class B conducted. XM version: EN55022 (CISPR11) Class A conducted.
|
|
|
|
Immunity
|
|
EN60601-1-2, EN61204-3
|
|
|
|
Harmonic Currents
|
|
EN61000-3-2
|
|
|
|
Voltage Flicker
|
|
EN61000-3-3
|
|
|
|
ESD Immunity
|
|
EN61000-4-2, Level 4 Perf criteria A
|
|
|
|
Radiated Immunity
|
|
EN61000-4-3, 10 V/m Perf criteria A
|
|
|
|
Conducted Immunity
|
|
EN61000-4-6, Level 3 Perf criteria A
|
|
|
|
EFT/Burst
|
|
EN61000-4-4, Level 3 Perf criteria A
|
|
|
|
Surge
|
|
EN61000-4-5, Level 3 Perf criteria A
|
|
|
|
Dips & Interruptions
|
|
EN61000-4-11, 30% 10 ms, 60% 100 ms, 100% 5000 ms, Perf Criteria A, B, B
|
|
|
|
Safety Approvals
|
|
EN60950-1, UL60950-1, CSA22.2 No. 60950-1-03, EN60601-1, UL60601-1, SEMI-F47
|
|
|